  1. Using a laser, or equivalent, determine ceiling level and secure perimeter edge trim to the wall at 400mm maximum centers.
  2. Cut lengths of suspension wire hangers to suit suspension depth, ensuring sufficient length for fixing.
  3. Setting out from the center of the room, secure hangers at 1000mm maximum centers to the structural soffit using fixings approved by the architect and determined by load and safety factor considerations. The first hangers are to be no more than 300mm from the wall. Where possible, not less than half tiles should be used at perimeters.
  4. To achieve a 600 x 600mm module, install main tees at 1200mm centers. Wire hangers to have a minimum of 3 turns to form a tight coil.
  5. Interlock 1200mm cross tees between main tees at 600mm centers and 600mm cross tees centrally between them.
  6. Tiles can now be offered into place.
  7. Cut perimeter tiles must be retained using wedges spaced at 300mm maximum centers.
 
 